Z-purlin and girt design calculator
ColdCalc designs continuous Z and C purlins and girts to AISI S100-24. It analyses the lapped member on a sloped roof with bending about both axes and warping torsion, then checks bending, shear, web crippling, bending with torsion, and wind uplift with the R factor of Section I6.2.1 at every support, lap end, brace and moment peak.
What you get
This is the result for the design the calculator opens on, computed by the ColdCalc engine when this page was built. Change any input in the calculator and it reruns in about a second.
| Check | S100-24 | Ratio | ||
|---|---|---|---|---|
| Bending, strong axis 27.00 ft, 1.2D + S | §F2.2, §F3.2, §F4 | 0.97 | NEAR | |
| Shear 23.00 ft, 1.2D + S | §G2.1 | 0.15 | OK | |
| Shear along the flanges 23.00 ft, 1.2D + S | §G2.1 | 0.04 | OK | |
| Web crippling 0.00 ft, 1.2D + S | §G5, EOF | 0.39 | OK | |
| Bending and shear combined 27.00 ft, 1.2D + S | §H2, Eq. H2-1 | 0.63 | OK | |
| Bending and web crippling combined 25.00 ft, 1.2D + S | §H3, Eq. H3-3 (nested Z) | 0.47 | OK | |
| Bending and torsion combined 27.00 ft, 1.2D + S | §H4, Eq. H4-1 (limit 1.25) | 0.97 | NEAR | |
| Deflection 40.00 ft, D + 0.7S | Appendix 1 | 0.67 | OK |
Z 8×2.5×0.085, Fy = 55 ksi, 2 spans of 25 ft and 25 ft, at 60 in. on center. AISI S100-24 LRFD, Direct Strength Method, finite strip buckling. A ratio is demand over available strength, or an interaction value over its limit; 1.00 or less passes.
What it checks
| Check | What it covers | AISI S100-24 |
|---|---|---|
| Bending | Lateral-torsional, local and distortional buckling in the spans, at lap ends and over supports | §F2, §F3, §F4 |
| Uplift on through-fastened purlins | The reduction factor R of Table I6.2.1-1 applied to the bending strength | §I6.2.1 |
| Bending and torsion | The bimoment from loads off the shear center, from a warping torsion analysis | §H4, §G8 |
| Shear, and bending with shear | Each member of a lap carries its share by stiffness | §G2, §H2 |
| Web crippling, and with bending | At rafters, including nested Z laps | §G5, §H3 |
| Deflection | Service-load deflection of the continuous member | Appendix 1 |
Every check opens to its limit states, each intermediate value with its equation number, and the φ or Ω applied. Strengths come from the Direct Strength Method by default, or the Effective Width Method, in LRFD or ASD.
What you enter
- A Z or C section by its dimensions, lipped or not, with any lip angle
- Spans, lap lengths at each interior support, and overhangs
- Roof slope and purlin spacing
- Dead, roof live, snow and wind loads, with uplift
- Anti-roll braces and other discrete braces
- Whether the panel is through-fastened to the top flange
- Bearing length at the rafters
How to use it
- 1Open the calculator and choose Purlin or girt. It starts on a lapped two-span Z-purlin.
- 2Set the section dimensions, spans, laps and roof slope.
- 3Enter the gravity loads and the wind uplift as pressures.
- 4Add anti-roll braces and say whether the panel is through-fastened.
- 5Read the governing check and click a lap end or the interior support to see the checks there.
Questions
How are lapped Z-purlins analysed?
As a continuous beam whose stiffness doubles inside each lap, where two purlins are nested. The moment over the support is shared by the two members by stiffness, and the critical points are usually the ends of the lap, where one purlin alone carries the moment, and the positive moment region of the end span.
What is the R factor for purlins?
Under wind uplift the compression flange of a through-fastened purlin is the free flange, restrained only partly by the panel. AISI S100-24 Section I6.2.1 gives the nominal strength as R times the local buckling strength of the fully braced section, with R from Table I6.2.1-1 by section type, depth and span condition, provided the listed conditions are met.
Does the calculator include torsion?
Yes. Loads applied on the flange of a Z or C act off the shear center and twist the purlin. ColdCalc runs a warping torsion analysis, reports the bimoment, and applies the Section H4 interaction of bending and torsion.
Can it check wall girts?
Yes. A girt is analysed the same way, with the wind acting as pressure and as suction. The same checks apply.
ColdCalc is a design aid. AISI S100-24 is the governing text, and results must be reviewed by the engineer responsible for the design. How the engine is tested against published examples, SSMA tables, CUFSM results and CFS reports is on the validation section of the home page.
How the checks work
Designing lapped Z-purlins: laps, anti-roll bracing and the R factor
How continuous lapped Z-purlins carry load, where they are checked, what anti-roll bracing does, and how the I6.2.1 R factor sets uplift strength for through-fastened roofs.
Web crippling of cold-formed steel joists and purlins (S100-24 §G5)
Why thin webs crush at supports and under point loads, the four load cases, how bearing length and fastening change the strength, and the H3 check with bending.
Local, distortional and global buckling of cold-formed steel, explained
The three ways a thin-walled steel member buckles, how to tell them apart on a signature curve, and how AISI S100-24 turns each into a strength. With finite strip results for a real stud.