Web crippling of cold-formed steel joists and purlins (S100-24 §G5)
Why thin webs crush at supports and under point loads, the four load cases, how bearing length and fastening change the strength, and the H3 check with bending.
- Web crippling is the local crushing and buckling of a thin web where a concentrated load or a support reaction enters it. AISI S100-24 checks it in §G5 with one empirical equation, Pn = Ct²Fy sin θ (1 − CR√(R/t))(1 + CN√(N/t))(1 − Ch√(h/t)) (Eq. G5-1).
- The coefficients, and the resistance and safety factors, come from Tables G5-1 to G5-5. Which row you use depends on the section type, the load case (EOF, IOF, ETF or ITF), whether the flange is fastened to the support, and for some section types whether the flanges are stiffened.
- Bearing length N matters. For an 800S200-54 joist, going from 1.5 in. to 6 in. of bearing raises the end reaction strength from 0.97 kip to 1.59 kip (LRFD).
- Over an interior support the web carries the reaction and the negative moment together, and §H3 limits the combination. In a two-span joist that can govern even when web crippling and bending each pass on their own.
Joists, purlins and girts sit on supports, and the reaction has to get into the member through its web. Hot-rolled steel design has a similar check, but a cold-formed joist's web is far more slender: it can be over a hundred times thinner than it is deep. Under a concentrated force it can fold over, buckle or crush locally while the rest of the member is far from its strength. That is web crippling, and for short, heavily loaded joists it can be the check that governs.
This article explains the S100-24 provisions, then works through them for an 800S200-54 floor joist with every number computed by ColdCalc's engine.
What web crippling is#
Picture a C-section joist sitting on a wall track. The reaction is concentrated over the bearing length N, and it enters the web through the curved corner between the bearing flange and the web. Close to the load, the web is in high local compression, it is bent by the eccentricity of the load at the corner, and it is slender. It fails by a combination of local yielding and buckling, usually as a fold near the loaded flange.
The Commentary to §G5 lists why a theoretical solution is impractical: non-uniform stress under the load, elastic and inelastic web stability, local yielding, bending from the load's eccentricity at the corner, initial imperfections, the restraint of the flanges, and inclined webs. So S100-24 uses an equation fitted to tests. The Commentary credits the unified equation with variable coefficients to Prabakaran and Schuster, and the current coefficients to Beshara's extension of that work.
Web crippling is a separate limit state from shear buckling of the web (§G2), which depends on the shear force over a length of web, not on how a force is concentrated.
The S100-24 web crippling equation, §G5#
Pn = Ct²Fy sin θ (1 − CR√(R/t))(1 + CN√(N/t))(1 − Ch√(h/t))
where:
- Pn is the nominal web crippling strength of one web;
- t is the web thickness, and Fy the design yield stress;
- θ is the angle between the plane of the web and the bearing surface, 45° ≤ θ ≤ 90°;
- R is the inside bend radius, N the bearing length (3/4 in. minimum), and h the flat depth of the web;
- C, CR, CN and Ch are coefficients from Tables G5-1 to G5-5.
Each bracket has a plain meaning. A tighter corner (smaller R/t) delivers the load into the web more directly, so strength falls as R/t grows. A longer bearing spreads the load, so strength rises with √(N/t). A more slender web (larger h/t) buckles sooner, so strength falls with √(h/t). The leading t² is why thickness matters most: the strength goes roughly with the square of the web thickness, but only linearly with Fy.
For a C- or Z-section with an overhang beyond an end support, §G5 permits Pnc = αPn (Eq. G5-2), with α = 1.34(Lo/h)0.26/(0.009(h/t) + 0.3) ≥ 1.0 (Eq. G5-3). It applies for 0.5 ≤ Lo/h ≤ 1.5 and h/t ≤ 154, and Pnc may not exceed the interior one-flange strength.
Pn is per web. For C-, Z- and hat sections and multi-web deck, multiply by the number of webs at the cross-section.
The four load cases: EOF, IOF, ETF and ITF#
§G5 defines the cases by distances measured in multiples of the flat web depth h:
| Case | Definition in §G5 |
|---|---|
| One-flange loading or reaction | The clear distance between the bearing edges of adjacent opposite concentrated loads or reactions is at least 1.5h |
| Two-flange loading or reaction | That clear distance is less than 1.5h: the web is squeezed between both flanges |
| End loading or reaction | The distance from the edge of the bearing to the end of the member is at most 1.5h |
| Interior loading or reaction | That distance is more than 1.5h |
Combining them gives end one-flange (EOF), interior one-flange (IOF), end two-flange (ETF) and interior two-flange (ITF). A joist on a wall, with nothing directly above the support, is EOF at its ends and IOF over an interior support. A joist end with a wall bearing on top of it and a wall below is ETF.
| Load case | Fastened, kip | Unfastened, kip |
|---|---|---|
| End one-flange (EOF) | 0.97 (0.85) | 0.91 (0.80) |
| Interior one-flange (IOF) | 2.05 (0.90) | 2.05 (0.90) |
| End two-flange (ETF) | 0.65 (0.85) | 0.76 (0.90) |
| Interior two-flange (ITF) | 2.15 (0.85) | 1.96 (0.80) |
End loading is much weaker than interior loading: at an end the web can only spread the load to one side. Two-flange loading at an end is weakest of all.
Fastened or unfastened#
Each table separates members whose flange is fastened to the support from those that are not. The Commentary explains why. Some test specimens in the literature were bolted to the bearing plate and some were not, which can make a considerable difference. Screwed specimens performed as well as bolted ones in control tests, and welding also counts. What matters is that the flange is restrained from rotating where the load is applied.
For single-web C-sections with stiffened flanges (Table G5-2), the fastened and unfastened one-flange rows share the same coefficients. Interior one-flange loading is identical in both. The difference is in the end factors: for end one-flange loading, fastened has φw = 0.85 and Ωw = 1.75, unfastened 0.80 and 1.85. Each two-flange row has its own coefficients, so fastened is not automatically higher. For this web the unfastened end two-flange row happens to give the slightly larger value, as the table above shows.
The coefficient tables by section type#
| Table | Section type | Limits on the table |
|---|---|---|
| G5-1 | Built-up sections (two channels back to back), per web | h/t ≤ 200, N/t ≤ 210, N/h ≤ 1.0, θ = 90° |
| G5-2 | Single web channel and C-sections | h/t ≤ 200, N/t ≤ 210, N/h ≤ 2.0, θ = 90° |
| G5-3 | Single web Z-sections | h/t ≤ 200, N/t ≤ 210, N/h ≤ 2.0, θ = 90° |
| G5-4 | Single hat sections, per web | h/t ≤ 200, N/t ≤ 200, N/h ≤ 2, θ = 90° |
| G5-5 | Multi-web deck sections, per web | h/t ≤ 200, N/t ≤ 210, N/h ≤ 3, 45° ≤ θ ≤ 90° |
Within each table the rows depend on fastening, the flange type (stiffened or partially stiffened, or unstiffened, for Tables G5-1 to G5-3), and the load case. Each row also has its own R/t limit. In Table G5-2 it ranges from R/t ≤ 1 for some unstiffened-flange cases to R/t ≤ 12 for fastened two-flange loading.
A few more conditions sit in the text around the tables:
- For interior two-flange loading of C- and Z-sections fastened to the support, the member must extend at least 2.5h beyond the edge of the bearing (1.5h when unfastened).
- The fastened ITF row of Table G5-2 applies only for an out-to-out depth d ≥ 4.5 in. The Commentary explains that tests on 3-1/2 in. C-sections found the equation unconservative by about 25 percent.
- Multi-web deck (Table G5-5) counts as unfastened for any support fastener spacing over 18 in.
- Webs with h/t greater than 200 must be given a means of transmitting concentrated loads or reactions directly into the web.
Resistance and safety factors vary by case#
Unlike most limit states, web crippling has no single φ or Ω. Each row of each table was calibrated on its own data and carries its own Ωw (ASD), φw (LRFD) and φw (LSD, Canada). For C-sections in Table G5-2, φw runs from 0.75 to 0.90 and Ωw from 1.65 to 2.00. Read the factors from the same row as the coefficients, and don't mix rows.
Worked example: an 800S200-54 floor joist#
The joist is the calculator's starting floor joist: an 800S200-54, 8 in. deep with 2 in. flanges, design thickness t = 0.0566 in., inside radius R = 0.0849 in. and Fy = 50 ksi. The flat web depth is h = 7.717 in., so h/t = 136.3 and R/t = 1.5, both inside the limits for Table G5-2. The flanges have lips, so they are stiffened, and they are screwed to the support.
At an end support with N = 1.5 in. (EOF, fastened: C = 4, CR = 0.14, CN = 0.35, Ch = 0.02):
Pn = 0.6407 × 0.8285 × 2.8018 × 0.7665 = 1.140 kip
The four factors are Ct²Fy (with sin 90° = 1), then the radius, bearing and slenderness brackets. The design strength is φwPn = 0.85 × 1.140 = 0.969 kip (LRFD), or Pn/Ωw = 0.651 kip (ASD).
Over an interior support the coefficients change (C = 13, CR = 0.23, CN = 0.14, Ch = 0.01) and Pn = 2.273 kip, about twice the end value.
Here is how the strength grows with bearing length:
| N, in. | End one-flange (EOF), kip | Interior one-flange (IOF), kip | ||||
|---|---|---|---|---|---|---|
| Pn | φwPn | Pn/Ωw | Pn | φwPn | Pn/Ωw | |
| 1.5 | 1.14 | 0.97 | 0.65 | 2.27 | 2.05 | 1.38 |
| 2.0 | 1.25 | 1.07 | 0.72 | 2.42 | 2.18 | 1.47 |
| 3.0 | 1.44 | 1.23 | 0.82 | 2.67 | 2.40 | 1.62 |
| 4.0 | 1.60 | 1.36 | 0.92 | 2.88 | 2.59 | 1.74 |
| 6.0 | 1.87 | 1.59 | 1.07 | 3.23 | 2.90 | 1.95 |
Quadrupling the bearing from 1.5 in. to 6 in. adds roughly 60 percent at the end, because the strength grows with √N, not N. At N = 6 in., N/t = 106 and N/h = 0.78, still inside the Table G5-2 limits.
What this means for the joist
As a single 14 ft span at 16 in. on center, with 15 psf dead and 40 psf live load plus self weight, the end reaction under 1.2D + 1.6L is 0.786 kip. Against φwPn = 0.969 kip that is a ratio of 0.81. Bending works at only 0.55 and deflection at 0.51. Web crippling governs this joist, ahead of bending. The usual fixes are more bearing, a bearing stiffener at the support (§G7), or a thicker joist.
Webs with holes, §G6#
§G6 covers C-section webs with holes near a load or reaction. Where a web hole is within the bearing length, a bearing stiffener is required. Otherwise the §G5 strength (Table G5-2) is multiplied by a reduction factor Rc:
Rc = 1.01 − 0.325dh/h + 0.083x/h ≤ 1.0
Rc = 0.90 − 0.047dh/h + 0.053x/h ≤ 1.0
Here dh is the depth of the hole and x the nearest distance between the hole and the edge of the bearing. The limits are dh/h ≤ 0.7, h/t ≤ 200, a hole centered at mid-depth, at least 18 in. clear between holes, at least d from the member end to the hole, corner radii ≥ 2t for noncircular holes with dh ≤ 2.5 in. and Lh ≤ 4.5 in., circular holes up to 6 in., and dh > 9/16 in. There is no Rc for two-flange loading. With a hole right at the edge of the bearing (x = 0), Eq. G6-2 gives at most 0.90, so an interior reaction next to a hole loses at least 10 percent.
Bearing stiffeners, §G7#
When the web alone is not enough, a bearing stiffener takes the load. §G7.1 covers compact stiffeners designed as compression members. Pn is the smaller of FwyAc (end crushing, Eq. G7.1-1) and the §E3.1 strength with an effective area Ab (column buckling), with Ωc = 2.00 and φc = 0.85. Ac and Ab add a strip of the joist web to the stiffener's own area: 18t² + As or b1t + As at an interior support or concentrated load, and 10t² + As or b2t + As at an end support.
§G7.2 covers the common site detail of a stud or track piece screwed to the joist web, for two-flange loading of C-sections. Pn = 0.7(Pwc + Pno) ≥ Pwc (Eq. G7.2-1), where Pwc is the Eq. G5-1 web crippling strength and Pno the stiffener's compressive strength from §E3 with Fn = Fy. Here Ωc = 1.70 and φc = 0.90. The limits are full bearing of the stiffener (half the strength if one stiffener flange is unsupported), a stiffener at least 3-1/2 in. deep and 0.0329 in. thick, at least three fasteners, the first at least d/8 from the joist flanges, a stiffener no shorter than the joist depth minus 3/8 in., and at least 1-1/2 in. of bearing. Stamped or rolled-in stiffeners (§G7.3) need tests or rational analysis.
Bending and web crippling at interior supports, §H3#
Over an interior support of a continuous joist or purlin the web carries the reaction and the largest negative moment at the same place. Both compress the web near the bottom flange, and the web can fail under the combination even when each is below its own strength. §H3 first requires M ≤ Mao and P ≤ Pa. Then, for shapes with a single unreinforced web:
0.91(P/Pn) + (M/Mno) ≤ 1.33φ, φ = 0.90, Ω = 1.70
P and M are the required reaction and the moment at or immediately next to it. Pn is the §G5 (or §G6) nominal strength, and Mno is the nominal flexural strength from §F3 with Fn = Fy or Mne = My: the local buckling strength of a laterally braced member. Note that Pn and Mno are nominal values. The φ is on the right-hand side.
Two more equations cover other shapes. Eq. H3-2, 0.88(P/Pn) + (M/Mno) ≤ 1.46φ, is for multiple unreinforced webs that restrain each other's rotation, such as I-sections of two back-to-back C-sections. Eq. H3-3, 0.86(P/Pn) + (M/Mno) ≤ 1.65φ (with φ = 0.90 LRFD, 0.80 LSD), is for two nested Z-shapes. It applies within h/t ≤ 150, N/t ≤ 140, Fy ≤ 70 ksi and R/t ≤ 5.5, and has bolting and fit-up conditions. Eq. H3-1 has an exception for deck or beams with two or more single webs at interior supports, when the compression edges are laterally supported and adjacent webs are no more than 10 in. apart.
Here is the 800S200-54 joist again, now continuous over two 14 ft spans with the same loads. The middle support carries about 1.25wL and the largest negative moment:
| N, in. | φwPn (IOF), kip | G5 ratio | P/Pn | M/Mno | H3 value / limit | H3 ratio |
|---|---|---|---|---|---|---|
| 1.5 | 2.05 | 0.96 | 0.865 | 0.492 | 1.278 / 1.197 | 1.07 |
| 2.0 | 2.18 | 0.90 | 0.812 | 0.492 | 1.231 / 1.197 | 1.03 |
| 3.0 | 2.40 | 0.82 | 0.737 | 0.492 | 1.162 / 1.197 | 0.97 |
| 4.0 | 2.59 | 0.76 | 0.683 | 0.492 | 1.114 / 1.197 | 0.93 |
With 1.5 in. of bearing, web crippling alone passes at the middle support, at a ratio of 0.96. But H3 does not: 1.278 against a limit of 1.197, a ratio of 1.07. Lengthening the bearing to 3 in. brings it to 0.97. The moment term doesn't change with N, so more bearing only works on the web crippling term. A bearing stiffener at the support is the other usual fix.
How ColdCalc checks web crippling in a member analysis#
For joists, purlins and any member with spans, ColdCalc checks web crippling as part of the member analysis rather than as a separate calculation:
- At every support that bears against the member. A support whose reaction opposes gravity is a bearing reaction. A reaction that holds the member down against uplift (wind on a roof purlin, for example) is carried by the connection, not by bearing, and is not checked for web crippling.
- Under concentrated loads that bear on a flange. Give a point load a bearing length and it is checked like a reaction, as unfastened. A load hung from the web or attached through a clip has no bearing length and is not checked.
- The load case from the geometry, following the §G5 definitions with h the flat depth of the web and every distance measured clear from the edge of the bearing. A bearing within 1.5h of the member end is end loading, otherwise interior; a bearing with another on the opposite flange closer than 1.5h is two-flange loading, as when a post sits on a joist right over its support. Interior two-flange loading of a fastened C or Z needs 2.5h to the member end, as Tables G5-2 and G5-3 require. The coefficients come from Table G5-2 for C-sections, Table G5-3 for Z-sections and Table G5-4 for hats. The flange type comes from the section (lipped flanges are stiffened), and the bearing length N and the fastened setting come from the design. The default bearing in the calculator is 1.5 in. for joists and 3 in. for purlins.
- Under every load combination, with the factors of the row in use.
- H3 wherever interior one-flange loading meets bending (over interior supports and under loads within a span) for C- and Z-sections, using Eq. H3-1 with the moment there, after the lead-in checks M ≤ Mao and P ≤ Pa.
- Laps. Where two purlins lap over a support, the reaction is shared equally between them, and each is checked for its share of the reaction and the moment. Two nested Z-sections use Eq. H3-3 when they meet its limits (h/t, N/t, Fy, R/t and a thickness ratio of at most 1.3), and Eq. H3-1 for each otherwise. See the Z-purlin article for laps.
Some cases are left for you to check separately: webs with holes at the support (§G6), the overhang increase of Eq. G5-2, and bearing stiffeners (§G7). ColdCalc's engine implements these provisions, but the member analysis does not apply them yet.
For the bending and shear checks that go with these, see the design guide, and for the local buckling strength that Mno uses, the Direct Strength Method article.
What is web crippling in cold-formed steel?
Web crippling is the local failure of a thin web, by yielding and buckling near the loaded flange, where a concentrated load or support reaction enters the member. Because cold-formed webs are very slender, it can govern joists and purlins at their supports. AISI S100-24 Section G5 gives the strength with Eq. G5-1 and coefficients from Tables G5-1 to G5-5.
What do EOF, IOF, ETF and ITF mean?
They are the four web crippling load cases: end one-flange, interior one-flange, end two-flange and interior two-flange. End means the bearing edge is within 1.5h of the member end; two-flange means opposite loads or reactions are closer than 1.5h, so the web is loaded through both flanges. h is the flat depth of the web.
How does bearing length affect web crippling strength?
Strength grows with the square root of N/t through the (1 + CN√(N/t)) term of Eq. G5-1. For a typical 8 in. joist, going from 1.5 in. to 6 in. of bearing raises the end reaction strength by roughly 60 percent. The minimum bearing length is 3/4 in., and Table G5-2 limits N/t to 210 and N/h to 2.0.
Does fastening the joist to the support increase web crippling strength?
Often, yes. Tables G5-1 to G5-5 have separate rows for flanges fastened to the support (by bolts, screws or welds) and unfastened flanges. For C-sections with stiffened flanges under one-flange loading the coefficients are the same, but the fastened end case has a higher resistance factor (0.85 against 0.80 for LRFD). For other cases the coefficients themselves differ.
When do I need to check combined bending and web crippling?
Wherever a concentrated load or reaction acts at a point of significant moment, most often over the interior supports of continuous joists and purlins. AISI S100-24 Section H3 requires 0.91(P/Pn) + M/Mno ≤ 1.33φ for single unreinforced webs (Eq. H3-1), with separate equations for back-to-back I-sections and nested Z-sections.
How do I increase the web crippling strength of a joist?
Lengthen the bearing, fasten the flange to the support, use a thicker section, or add a bearing stiffener designed to AISI S100-24 Section G7. A stud or track stiffener screwed to the web is covered by Section G7.2 for two-flange loading of C-sections.