Cold-formed steel joist and beam calculator
ColdCalc checks a cold-formed steel joist, rafter, header or beam to AISI S100-24. Enter the section, the spans and the floor or roof loads; it analyses the member over one span or several and checks bending, shear, web crippling at each support, their interactions, and live-load and total deflection.
What you get
This is the result for the design the calculator opens on, computed by the ColdCalc engine when this page was built. Change any input in the calculator and it reruns in about a second.
| Check | S100-24 | Ratio | ||
|---|---|---|---|---|
| Bending, strong axis 7.00 ft, 1.2D + 1.6L | §F2.2, §F3.2, §F4 | 0.55 | OK | |
| Shear 0.00 ft, 1.2D + 1.6L | §G2.1 | 0.18 | OK | |
| Web crippling 0.00 ft, 1.2D + 1.6L | §G5, EOF | 0.81 | OK | |
| Bending and shear combined 7.00 ft, 1.2D + 1.6L | §H2, Eq. H2-1 | 0.55 | OK | |
| Deflection 7.00 ft, L | Appendix 1 | 0.51 | OK |
800S200-54, Fy = 50 ksi, 14 ft span, at 16 in. on center. AISI S100-24 LRFD, Direct Strength Method, finite strip buckling. A ratio is demand over available strength, or an interaction value over its limit; 1.00 or less passes.
What it checks
| Check | What it covers | AISI S100-24 |
|---|---|---|
| Bending | Lateral-torsional, local and distortional buckling, in positive and negative moment | §F2, §F3, §F4 |
| Shear | Web shear yielding and buckling | §G2 |
| Web crippling | At every support and bearing point load: end or interior, one-flange or two-flange | §G5 |
| Bending and web crippling | Over interior supports, where the reaction and the moment peak together | §H3 |
| Bending and shear | The interaction along the span | §H2 |
| Bearing stiffeners | Where a stiffener replaces web crippling | §G7 |
| Deflection | Live-load and total-load deflection with the effective moment of inertia | Appendix 1 |
Every check opens to its limit states, each intermediate value with its equation number, and the φ or Ω applied. Strengths come from the Direct Strength Method by default, or the Effective Width Method, in LRFD or ASD.
What you enter
- An SSMA joist section such as 800S200-54, or a custom C, Z, track or hat
- One span or several, with overhangs
- Dead, live, roof live, snow and wind loads as pressures
- Spacing, and whether a deck braces the top flange
- Blocking or bridging of the bottom flange
- Bearing length at the supports, and whether the flange is fastened
- Web holes and bearing stiffeners, where there are any
How to use it
- 1Open the calculator and choose Joist or beam. It starts on an 800S200-54 floor joist.
- 2Set the spans and supports, then the dead and live loads in psf and the joist spacing.
- 3Say whether a deck braces the top flange and where the bottom flange is blocked.
- 4Set the bearing length at the supports for web crippling.
- 5Read the governing check, and click a support to see web crippling and Eq. H3 there.
Questions
How far can a cold-formed steel joist span?
It depends on the section, the spacing, the loads and the deflection limit, and on web crippling at the supports. A span table gives the answer for one set of assumptions. ColdCalc checks your joist for your loads to AISI S100-24, and Compare sizes lists every SSMA section that passes for your span.
What is web crippling and when does it govern?
Web crippling is local crushing of the thin web under a concentrated load or reaction. It often governs short joists with heavy loads and joists continuous over a support, where it is also checked together with bending (Section H3). Longer bearing or a bearing stiffener raises the strength.
Does it handle continuous joists and overhangs?
Yes. Any number of spans with overhangs at either end. The analysis finds the moments, shears and reactions under every load combination, and the checks run at each support, load point and moment peak.
Does it check deflection?
Yes. Live-load and total-load deflection are checked against limits you set, such as L/360 and L/240, using the effective moment of inertia of AISI S100-24 Appendix 1 at service load.
ColdCalc is a design aid. AISI S100-24 is the governing text, and results must be reviewed by the engineer responsible for the design. How the engine is tested against published examples, SSMA tables, CUFSM results and CFS reports is on the validation section of the home page.
How the checks work
Web crippling of cold-formed steel joists and purlins (S100-24 §G5)
Why thin webs crush at supports and under point loads, the four load cases, how bearing length and fastening change the strength, and the H3 check with bending.
Cold-formed steel floor joist spans: a span table and what limits it
How far a steel floor joist spans, and why: bending, shear, web crippling and deflection to AISI S100-24, a worked joist, and a span table computed for 12, 16 and 24 in. spacing.
Effective Width Method vs Direct Strength Method: when they differ, and why
How the two AISI S100 methods model local and distortional buckling, where their answers diverge for studs and tracks, and how to choose between them.