Steel stud limiting heights: what sets them, with a height table
What a limiting height is, how strength and deflection (L/240, L/360, L/600) set it, the assumptions behind any table, and wall stud heights computed to AISI S100-24 for wind.
- A stud's limiting height is the tallest it can stand under a given lateral load: the lesser of the height at which its strength runs out (bending, with shear) and the height at which its deflection reaches the limit (L/240, L/360 or L/600).
- Under 30 psf of wind at 16 in. on center, a 600S162-43 stud braced every 48 in. is good for 18′-8″ at L/240, 18′-2″ at L/360 and 15′-4″ at L/600.
- Which limit governs depends on the deflection criterion. In the table below, strength sets 12 of 18 heights at L/240, 5 at L/360 and none at L/600.
- Bracing matters as much as the stud. The same 600S162-43 with a single brace at mid-height drops from 18′-8″ to 15′-11″.
- The tables are computed by ColdCalc's engine to AISI S100-24 for wind alone. A stud that also carries axial load needs a beam-column check.
Limiting height tables are how most curtain wall and partition studs get chosen: find the wind pressure, find the deflection limit, read down to the first stud that is tall enough. This article explains what goes into such a table, works one stud through, and gives limiting heights computed by ColdCalc so the assumptions are all in view.
What a limiting height is#
A wall stud under wind is a beam standing on end. It spans from the bottom track to the top track, and the wind on its tributary width loads it uniformly. With pinned ends:
Two heights follow. One is where the factored moment reaches the available bending strength. The other is where the service deflection reaches H divided by the limit. The limiting height is the lesser.
Moment grows with H² and deflection with H⁴, so the two criteria respond differently to the stud. A stronger steel raises the strength height and leaves the deflection height where it was, because stiffness depends on the modulus of elasticity, which is the same for every grade.
The assumptions behind the numbers#
Every limiting height table rests on a set of assumptions, and tables from different sources differ mostly because the assumptions do. These are the ones used here.
- Wind load level. ASCE 7-22 wind pressures are strength-level: the LRFD load factor on W is 1.0. Older tables were built on service-level (ASD) pressures. Enter a table with the kind of pressure it was made for.
- Deflection at 0.42W. IBC Table 1604.3, footnote f, permits the wind load for checking the deflection of components and cladding to be taken as 0.42 times the component and cladding load. ColdCalc's generated service combination for wind is 0.42W.
- Deflection limit. Building codes set limits by finish: commonly L/240 for brittle finishes and L/360 for plaster and stucco. L/600 is commonly specified behind brick veneer. The limit is a project decision.
- Bracing. Both flanges are braced against lateral movement and twist every 48 in., as bridging does. The unbraced length for lateral-torsional buckling (§F2) is that spacing.
- Non-composite. Sheathing is not counted, for strength or for stiffness. Manufacturers' tables for interior partitions are often composite: based on tests of studs with gypsum board attached, and taller for it.
- Wind only. No axial load. See below for bearing walls.
- Unpunched webs, and no end checks. Web crippling at the tracks and the stud-to-track connection are separate.
One stud, worked through#
Take a 600S162-43 (6 in. deep, 1-5/8 in. flanges, 43 mil, Fy = 33 ksi) at 16 in. on center under 30 psf.
- Line load. 30 psf × 16 in. / 12 = 40 plf. The strength combination is 1.0W.
- Strength height. The available bending strength φMn, the least of lateral-torsional (§F2), local (§F3) and distortional (§F4) buckling by the Direct Strength Method, is 20.9 kip·in. Setting wH²/8 equal to it gives H = 18′-8″, where Mu = 20.9 kip·in. Shear is small (0.15), and the combined bending and shear check of §H2 is 0.99.
- Deflection at that height. Under 0.42W, 16.8 plf, the stud deflects 0.67 in., which is L/333. That meets L/240, so strength sets the limiting height at L/240: 18′-8″.
- Tighter limits. L/333 does not meet L/360 or L/600, so the stud has to be shorter: 18′-2″ for L/360 and 15′-4″ for L/600.
| Check | Ratio |
|---|---|
| Bending, strong axis | 1.00 |
| Shear | 0.15 |
| Bending and shear combined | 0.99 |
| Deflection | 0.72 |
Limiting height table#
| Wind | Stud | L/240 | L/360 | L/600 |
|---|---|---|---|---|
| 20 psf | 362S162-33 | 14′-2″ s | 12′-10″ | 10′-10″ |
| 20 psf | 362S162-43 | 16′-0″ | 14′-0″ | 11′-10″ |
| 20 psf | 600S162-33 | 18′-11″ s | 18′-11″ s | 16′-1″ |
| 20 psf | 600S162-43 | 22′-10″ s | 20′-9″ | 17′-6″ |
| 20 psf | 600S162-54 | 25′-6″ | 22′-4″ | 18′-10″ |
| 20 psf | 800S162-54 | 32′-3″ | 28′-2″ | 23′-9″ |
| 30 psf | 362S162-33 | 11′-7″ s | 11′-3″ | 9′-6″ |
| 30 psf | 362S162-43 | 13′-6″ s | 12′-3″ | 10′-4″ |
| 30 psf | 600S162-33 | 15′-5″ s | 15′-5″ s | 14′-1″ |
| 30 psf | 600S162-43 | 18′-8″ s | 18′-2″ | 15′-4″ |
| 30 psf | 600S162-54 | 22′-4″ | 19′-6″ | 16′-5″ |
| 30 psf | 800S162-54 | 28′-2″ | 24′-7″ | 20′-9″ |
| 40 psf | 362S162-33 | 10′-0″ s | 10′-0″ s | 8′-7″ |
| 40 psf | 362S162-43 | 11′-9″ s | 11′-1″ | 9′-4″ |
| 40 psf | 600S162-33 | 13′-4″ s | 13′-4″ s | 12′-9″ |
| 40 psf | 600S162-43 | 16′-2″ s | 16′-2″ s | 13′-11″ |
| 40 psf | 600S162-54 | 20′-3″ | 17′-8″ | 14′-11″ |
| 40 psf | 800S162-54 | 25′-2″ s | 22′-4″ | 18′-10″ |
How to read it:
- L/240 is mostly a strength table. With deflection checked at 0.42W, strength sets 12 of the 18 heights. The exceptions are nearly all 50 ksi studs, which are strong enough for deflection to catch up.
- L/600 is a stiffness table. Deflection sets every height. Steel grade makes no difference there: only the moment of inertia does.
- Depth beats thickness. A 600S162-43 stands more than a third taller on strength than a 362S162-43 at every pressure in the table. A 600S162-33 has about the same weight of steel as a 362S162-43 (1.17 plf against 1.16 plf) and stands taller in every column.
- Height falls slowly with pressure. Strength height varies with 1/√w and deflection height with 1/∛w. Doubling the wind from 20 to 40 psf takes about 30 % off a strength-governed height and about 20 % off a deflection-governed one.
Bracing changes the answer#
The strength heights above depend on the 48 in. brace spacing. Between braces the compression flange can buckle sideways and twist, and §F2 reduces the strength accordingly. Wind blows both ways, so each flange takes its turn in compression.
With one brace at mid-height in place of bracing every 48 in., the example stud's strength height drops from 18′-8″ to 15′-11″. Sheathing fastened to a flange braces it for as long as the sheathing is there and able to do the job. Sheathing on one side only leaves the other flange relying on the bridging when it is in compression. The buckling modes article explains what bracing does and does not restrain.
When the stud also carries axial load#
A bearing wall stud has axial compression with the wind moment, and a limiting height table no longer applies. The check becomes the interaction of §H1.2,
with the moment amplified for the axial load (second-order effects) and the axial strength governed by flexural, torsional or flexural-torsional buckling between braces. Axial load uses up capacity quickly, and it lowers the height at which the stud works. The wall stud design example goes through that calculation step by step.
Using limiting heights sensibly#
- Match the table to the project: the wind level (strength or service), the deflection factor, the bracing and whether the table is composite.
- Check the ends. A tall stud under high wind delivers a real reaction to the track. Web crippling (§G5) and the screws into the track need their own checks, and deflection track details at the head change the support.
- Punchouts reduce shear strength near the ends (§G3). They matter little for bending at mid-height.
- Openings. Jamb studs beside windows and doors collect load from the header and sill and are not covered by a table of typical studs.
- Run the actual stud when anything is unusual. It takes less time than interpolating.
What is the limiting height of a steel stud?
It is the greatest height at which a stud of a given size and spacing can span between the bottom and top tracks under a given lateral load without exceeding its strength or its deflection limit. It is the lesser of a strength-governed height, from bending and shear to AISI S100, and a deflection-governed height for a limit such as L/240, L/360 or L/600.
How tall can a 6 inch steel stud be?
It depends on thickness, spacing, wind pressure, deflection limit and bracing. As computed by ColdCalc to AISI S100-24 for studs at 16 in. on center braced every 48 in., non-composite, under 30 psf of strength-level wind, a 600S162-43 stud is good for about 18 ft 8 in. at L/240, 18 ft 2 in. at L/360 and 15 ft 4 in. at L/600.
What deflection limit should I use for exterior steel stud walls?
Building codes set limits by finish: commonly L/240 for brittle finishes and L/360 for plaster and stucco, with L/120 for flexible finishes. L/600 or tighter is commonly specified for studs backing brick veneer. The limit is set by the project and the cladding, not by AISI S100.
Is deflection checked under the full wind load?
Not usually. IBC Table 1604.3, footnote f, permits the wind load to be taken as 0.42 times the components and cladding load when checking deflection. Strength is checked under the full factored wind, which is 1.0W in LRFD with ASCE 7-22 pressures.
What is the difference between composite and non-composite limiting heights?
Non-composite heights are calculated for the steel stud alone. Composite heights count the sheathing, usually gypsum board on both faces, as acting with the stud, and are based on tests of the assembly. Composite heights are taller and apply only when the sheathing is installed full height as tested.
Does a higher yield strength increase the limiting height?
Only where strength governs. A 50 ksi stud is stronger in bending than a 33 ksi stud of the same size, but no stiffer, because the modulus of elasticity is the same. Where the deflection limit governs, as it does at L/600, the grade makes no difference.