1000S300-54 stud properties and strength

SSMA 10 in stud or joist, 3 in flange, 54 mil (0.0566 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 1000S300-54 has an area of 0.953 in² and weighs 3.24 lb/ft. Its strong-axis moment of inertia is 14.076 in⁴ gross and 11.093 in⁴ effective at yield, and its effective section modulus is 1.905 in³. With the flange braced, its allowable moment is 54.2 kip·in (ASD), governed by distortional buckling (§F4).

10″3″0.625″ lipt = 0.0566″

Dimensions

Depth10in
Flange width3in
Lip length0.625in
Design thickness0.0566in
Minimum thickness0.0538in
Inside bend radius0.0849in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A0.953in²
Weight3.24lb/ft
Ix14.076in⁴
Sx2.815in³
rx3.844in
Iy1.024in⁴
Sy0.452in³
ry1.037in

Torsion and effective section

J1.017×10⁻³ in⁴
Cw19.248in⁶
xo-1.886in
ro4.405in
β0.817
Ixe at yield11.093in⁴
Sxe1.905in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)90.4554.1681.41§F4 · kip·in
Strong-axis moment, flange braced (EWM)90.4354.1581.39§F4 · kip·in
Shear, web without holes4.362.613.93§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)15.808.7813.43§E3.2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)15.808.7813.43§E3.2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)15.798.7713.42§E3.2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)15.778.7613.41§E3.2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)15.728.7313.36§E3.2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)15.518.6213.19§E3.2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.01101001000half-wavelength, in (log scale)load factor (P/Py)Local0.10 at 7.5 inDistortional (by cFSM)0.21 at 31.2 in
Signature curve of the 1000S300-54 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.01101001000half-wavelength, in (log scale)load factor (M/My)Local0.53 at 5.5 inDistortional0.57 at 26.3 in
Signature curve of the 1000S300-54 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py47.63kip
Pcrℓ at 7.54.72kip
Pcrd at 31.29.77kip
My140.76kip·in
Mcrℓ at 5.574.47kip·in
Mcrd at 26.379.69kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
4.72 kip at 7.5 in
Distortional
9.77 kip at 31.2 in
Buckled shapes of the 1000S300-54 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 1000S300-54 mean?

1000S300-54 is an SSMA designation: 10 in stud or joist, 3 in flange, 54 mil (0.0566 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0566 in.

What are the section properties of a 1000S300-54 stud?

Area 0.953 in², weight 3.24 lb/ft, Ix 14.076 in⁴, Sx 2.815 in³, rx 3.844 in, Iy 1.024 in⁴, ry 1.037 in, J 1.017 ×10⁻³ in⁴, Cw 19.248 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 1000S300-54?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 90.5 kip·in by the Direct Strength Method (governed by §F4): 54.2 kip·in allowable (ASD) or 81.4 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 1000S300-54?

By finite strip analysis, local buckling in compression occurs at 4.72 kip (half-wavelength 7.5 in) and distortional buckling at 9.77 kip (31.2 in), against a squash load Py of 47.63 kip.

Other 10 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation