600S250-97 stud properties and strength

SSMA 6 in stud or joist, 2-1/2 in flange, 97 mil (0.1017 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 600S250-97 has an area of 1.169 in² and weighs 3.98 lb/ft. Its strong-axis moment of inertia is 6.497 in⁴ gross and 6.351 in⁴ effective at yield, and its effective section modulus is 2.082 in³. With the flange braced, its allowable moment is 60.5 kip·in (ASD), governed by distortional buckling (§F4).

6″2-1/2″0.625″ lipt = 0.1017″

Dimensions

Depth6in
Flange width2-1/2in
Lip length0.625in
Design thickness0.1017in
Minimum thickness0.0966in
Inside bend radius0.1526in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A1.169in²
Weight3.98lb/ft
Ix6.497in⁴
Sx2.166in³
rx2.358in
Iy0.923in⁴
Sy0.529in³
ry0.889in

Torsion and effective section

J4.030×10⁻³ in⁴
Cw6.443in⁶
xo-1.795in
ro3.093in
β0.663
Ixe at yield6.351in⁴
Sxe2.082in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)101.0860.5390.97§F4 · kip·in
Strong-axis moment, flange braced (EWM)101.0660.5290.96§F4 · kip·in
Shear, web without holes14.898.9213.40§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)38.9521.6433.11§E3.2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)38.8521.5933.03§E3.2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)38.7021.5032.89§E3.2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)37.9521.0832.26§E3.2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)36.0720.0430.66§E3.2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)33.3318.5228.33§E3.2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.02.51101001000half-wavelength, in (log scale)load factor (P/Py)Local0.89 at 4.6 inDistortional1.08 at 16.2 in
Signature curve of the 600S250-97 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.03.54.04.55.05.56.06.57.07.58.08.59.09.51101001000half-wavelength, in (log scale)load factor (M/My)Local4.12 at 3.4 inDistortional2.05 at 15.1 in
Signature curve of the 600S250-97 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py58.45kip
Pcrℓ at 4.652.01kip
Pcrd at 16.263.07kip
My108.28kip·in
Mcrℓ at 3.4445.91kip·in
Mcrd at 15.1221.47kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
52.01 kip at 4.6 in
Distortional
63.07 kip at 16.2 in
Buckled shapes of the 600S250-97 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 600S250-97 mean?

600S250-97 is an SSMA designation: 6 in stud or joist, 2-1/2 in flange, 97 mil (0.1017 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.1017 in.

What are the section properties of a 600S250-97 stud?

Area 1.169 in², weight 3.98 lb/ft, Ix 6.497 in⁴, Sx 2.166 in³, rx 2.358 in, Iy 0.923 in⁴, ry 0.889 in, J 4.030 ×10⁻³ in⁴, Cw 6.443 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 600S250-97?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 101.1 kip·in by the Direct Strength Method (governed by §F4): 60.5 kip·in allowable (ASD) or 91.0 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 600S250-97?

By finite strip analysis, local buckling in compression occurs at 52.01 kip (half-wavelength 4.6 in) and distortional buckling at 63.07 kip (16.2 in), against a squash load Py of 58.45 kip.

Other 6 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation