# Cold-formed steel floor joist spans: a span table and what limits it

> How far a steel floor joist spans, and why: bending, shear, web crippling and deflection to AISI S100-24, a worked joist, and a span table computed for 12, 16 and 24 in. spacing.

By ColdCalc Engineering. Published 2026-11-24. Source: https://www.coldcalc.com/blog/cold-formed-steel-joist-span

- A cold-formed steel floor joist span is set by four things: **bending** strength (§F3, §F4), **shear** (§G2), **web crippling** at the supports (§G5) and **deflection**. With the subfloor bracing the top flange, lateral-torsional buckling does not apply.
- For a residential floor (15 psf dead, 40 psf live), an 800S162-54 joist at 16 in. on center spans 16′-9″, a 1000S162-54 spans 19′-8″ and a 1200S200-68 spans 26′-0″, when the web is stiffened at the supports.
- At 12 and 16 in. spacing most of these joists are limited by live load deflection (L/360). At 24 in. bending usually takes over.
- Without web stiffeners, **web crippling** on a 1.5 in. bearing shortens the span of most joists in the table, and of every one at 24 in. on center. Check the supports before trusting any span table.
- The table below is computed by ColdCalc's engine to AISI S100-24, every cell from a full member design.

"How far can a steel joist span?" has no single answer, because the span depends on the load, the spacing, the deflection limit, the bracing and, more than most people expect, the support detail. This article works one joist through, explains each limit, and gives a span table in which every value is the result of a complete AISI S100-24 design, not a formula.

## What limits a joist span

A floor joist is a C-section on its side: web vertical, the subfloor fastened to the top flange, a simple span between a wall or beam at each end. Uniform load w on a span L gives the three demands every beam table starts from:

    M = wL²/8, V = R = wL/2, δ = 5wL⁴/(384EI)

The moment grows with L², the end reaction with L and the deflection with L⁴. Each is checked against a different part of the Specification:

| Limit | S100-24 | What happens |
| --- | --- | --- |
| Bending | §F3 local and §F4 distortional buckling | The compression flange and the web buckle before the section yields. With the top flange held by the subfloor, lateral-torsional buckling (§F2) is prevented. |
| Shear | §G2, and §H2 with bending | The web buckles in shear near the supports. It rarely governs a simple span under uniform load. |
| Web crippling | §G5 | The thin web crushes above the bearing where the end reaction enters. |
| Deflection | Building code limits | Usually L/360 under live load and L/240 under total load. |

A joist "spans" a distance when all four pass. Which one fails first changes with the joist and its spacing, as the table shows.

## One joist, worked through

Take the starting design of ColdCalc's Floor joist calculator: an 800S200-54 (8 in. deep, 2 in. flanges, 54 mil, Fy = 50 ksi) at 16 in. on center, with 15 psf dead load, the joist's own weight and 40 psf live load. The longest span that passes with the web stiffened at the supports is 17′-6″.

1. **Line loads.** At 16 in. on center each joist carries 20.0 plf dead, 2.47 plf self weight and 53.3 plf live. The governing strength combination is 1.2D + 1.6L: wu = 112.3 plf.
2. **Bending.** Mu = wuL²/8 = 51.6 kip·in. The available strength φMn, the lesser of local and distortional buckling by the Direct Strength Method, is 60.1 kip·in. Ratio 0.86.
3. **Shear.** Ratio 0.22, at the supports. The combined bending and shear check of §H2 is 0.85, no worse than bending alone, because the shear is largest where the moment is zero.
4. **Deflection.** Under live load alone the joist deflects 0.580 in. against a limit of 0.583 in. (L/360). This is the check that sets the span.
5. **Web crippling.** The factored end reaction is wuL/2 = 0.98 kip. On a 1.5 in. bearing, fastened to the support, the available end one-flange strength is 0.97 kip: a ratio of 1.01, just over. Without a stiffener the span has to come down to 17′-3″. With 3.5 in. of bearing the ratio is 0.76 and the full span stands.

| Check | Ratio |
| --- | --- |
| Bending, strong axis | 0.86 |
| Shear | 0.22 |
| Bending and shear combined | 0.85 |
| Deflection | 1.00 |

*800S200-54 at 16 in. on center spanning 17′-6″, web stiffened at the supports. A ratio is demand over available strength, or deflection over its limit. Computed by ColdCalc.*

Open this joist in ColdCalc

800S200-54 at 16 in. on center, spanning 17′-6″. Change the section, span, loads, bearing or supports and every check reruns.

Open the joist

## Span table

Every cell is the longest span, to the inch, at which the joist passes all of the checks above. The assumptions are in the caption. Read them before using a value, because each one moves the answer.

| Joist | 12 in. o.c., stiffened | 12 in. o.c., 1.5 in. bearing | 16 in. o.c., stiffened | 16 in. o.c., 1.5 in. bearing | 24 in. o.c., stiffened | 24 in. o.c., 1.5 in. bearing |
| --- | --- | --- | --- | --- | --- | --- |
| 800S162-43 | 15′-0″ B | 9′-11″ | 13′-0″ B | 7′-6″ | 10′-8″ B | 5′-0″ |
| 800S162-54 | 18′-5″ D | 18′-5″ | 16′-9″ D | 16′-9″ | 14′-6″ B | 11′-7″ |
| 800S200-54 | 19′-3″ D | 19′-3″ | 17′-6″ D | 17′-3″ | 15′-3″ D | 11′-7″ |
| 1000S162-54 | 21′-11″ D | 21′-10″ | 19′-8″ B | 16′-6″ | 16′-1″ B | 11′-1″ |
| 1000S162-68 | 23′-9″ D | 23′-9″ | 21′-7″ D | 21′-7″ | 18′-10″ B | 17′-0″ |
| 1200S200-68 | 28′-7″ D | 28′-7″ | 26′-0″ D | 24′-3″ | 22′-1″ B | 16′-5″ |

*Longest simple span of a single joist under 15 psf dead load plus self weight and 40 psf live load, to AISI S100-24 (LRFD, ASCE 7-22 combinations, Direct Strength Method with finite strip buckling), with live load deflection limited to L/360 and total to L/240. The top flange is braced by the subfloor. "Stiffened" has web stiffeners at the supports, so web crippling is not a limit; the letter is the check that sets the span (B = bending, D = deflection). "1.5 in. bearing" has no stiffeners and an end bearing of 1.5 in. with the flange fastened to the support. Spans are in feet and inches, rounded down to the inch. Steel: 43 mil, Fy = 33 ksi; 54 and 68 mil, Fy = 50 ksi. No web holes. Computed by ColdCalc; not a substitute for a design.*

Some patterns are worth knowing:

- **Deflection governs the closer spacings.** At 12 in. on center every 50 ksi joist in the table is limited by L/360. Their strength is not used up: the example joist reaches its span at a bending ratio of 0.86.
- **Bending takes over at 24 in.** Wider spacing raises the load on each joist. Strength demand grows in proportion while the deflection limit stays L/360, so strength catches up.
- **The 33 ksi joist is always strength-limited.** The 800S162-43 is the only 33 ksi joist here, and bending sets its span at every spacing.
- **Depth is worth more than flange width.** At 12 in. on center, going from 800S162-54 to 800S200-54 adds 10 in. of span. Going to 1000S162-54 adds 42 in. instead.
- **Web crippling is the catch.** The "1.5 in. bearing" columns are shorter than the "stiffened" ones in 12 of 18 cells, and in every cell at 24 in. on center. A deeper web is no help: the 1000S162-54 at 24 in. is limited to 11′-1″, less than the 800S162-54 at 11′-7″, because a more slender web cripples at a lower load.

## Getting past web crippling

The end reaction has to get from the web into the support. Four things raise what the web can take:

- **A longer bearing.** Strength grows with the square root of the bearing length over the thickness. In the example, 3.5 in. of bearing in place of 1.5 in. drops the ratio from 1.01 to 0.76.
- **Fastening the flange to the support.** Tables G5-1 to G5-5 have separate rows for fastened and unfastened flanges.
- **A web stiffener.** A stud or track section screwed to the web at the support, designed to §G7. This is what the "stiffened" columns assume.
- **A thicker joist.** Web crippling strength grows with about the square of the thickness.

The [web crippling article](https://www.coldcalc.com/blog/web-crippling-cold-formed-steel) covers the four load cases, Eq. G5-1 and the coefficients. Continuous joists need one more check: over an interior support the reaction and the moment peak together, and §H3 combines them.

## What a span table cannot tell you

A table fixes the assumptions. Your floor may not match them.

- **Loads.** 40 psf live is a residential floor. Offices, corridors and assembly areas are higher, and partitions, tile and mechanical loads add dead load. Line loads from walls above and point loads from posts need their own analysis.
- **Deflection limits.** L/360 is a code minimum for floors. Stiff finishes and long spans often call for L/480 or tighter, and floor vibration is a separate question that no strength check answers.
- **Web holes.** The table is for unpunched webs. Holes near a support reduce shear strength (§G3) and web crippling strength (§G6).
- **Continuity.** Two-span joists have smaller mid-span moments but a large negative moment and reaction at the middle support, where the bottom flange is in compression and is not braced by the subfloor.
- **Bracing during construction.** Before the subfloor is on, nothing holds the top flange.
- **Connections.** Joist to rim track, hangers and stiffener screws are designed separately. See [screw connections](https://www.coldcalc.com/blog/screw-connections-cold-formed-steel).

For anything outside the table, run the joist itself. The designation system used here (800S162-54 is 8 in. deep, 1-5/8 in. flange, 54 mil) is explained in the [SSMA designation article](https://www.coldcalc.com/blog/ssma-stud-designation), and the order of a full member check in the [design guide](https://www.coldcalc.com/blog/cold-formed-steel-design-guide).

**How far can a cold-formed steel floor joist span?**

It depends on the joist, spacing, loads, deflection limit and support detail. As computed by ColdCalc to AISI S100-24 for 15 psf dead and 40 psf live load with L/360 live load deflection and stiffened supports, typical 8 in. joists of 54 mil steel at 16 in. on center span about 17 ft, 10 in. joists about 20 ft, and 12 in. joists of 68 mil steel about 26 ft.

**What usually governs the span of a steel floor joist?**

At 12 and 16 in. spacing, live load deflection (L/360) usually governs joists of 50 ksi steel. At 24 in. spacing, and for 33 ksi joists, bending strength usually governs. Where the joist has no web stiffener at its supports, web crippling under the end reaction often governs before either.

**Do steel floor joists need web stiffeners at the supports?**

Often, yes. The end reaction can exceed the web crippling strength of AISI S100-24 Section G5 well before the joist reaches its bending or deflection limit, especially at 24 in. spacing and with short bearing lengths. A longer bearing, fastening the flange to the support, a thicker joist or a web stiffener designed to Section G7 each raise the strength.

**What deflection limit applies to cold-formed steel floor joists?**

Building codes commonly require L/360 under live load and L/240 under total load for floors. Many designers use L/480 or tighter under live load for long spans, brittle finishes or to reduce perceptible vibration. The limit is a project decision, not an AISI S100 requirement.

**Does closer joist spacing increase the span?**

Yes. Closer spacing reduces the load each joist carries. Strength-governed spans grow with the square root of the reduction in load, and deflection-governed spans with its cube root, so going from 24 in. to 16 in. on center typically adds about 15 to 22 percent to the span.

**Is lateral-torsional buckling a concern for floor joists?**

Not for a simple span once the subfloor is fastened to the top flange, because the compression flange is braced along its length. It is a concern during construction before the subfloor is installed, and near interior supports of continuous joists, where the bottom flange is in compression.